IUC-7X-PWM: Isolated PWM Converter               specsheet 

 
    
    Features:
  • DIN-Rail Mounted (small size)
  • Wide Input PWM Range (from 5Hz to 3KHz)
  • Industry Standard Output: 4-20 mA, 1-5 VDC, and more....
  • Easy Field Calibration (Typ. calibration time < 2 min. using handheld meter only)
  • Microprocessor Controlled for High Accuracy
  • 24 VDC Supply for Open Collector  Input or Dry Contact Input.
  • Power: 24 VDC
  • High Noise Rejection
  • CSA and NRTL Approved
Function:
The IUC-7X-FRX is a microprocessor controlled PWM to analog output converter/isolator that is easily field configurable to and PWM input from 0-5 Hz to 0-2 KHz. Adjustments to the input settings can be made while the instrument is operating. This flexibility combined with easy field calibration allows for the fine tuning of a process on site with lettle effort. All that is required to change the calibration settings is a voltmeter and a small screwdriver.

The IUC-7X-PWM operates over a wide duty cycle range of at least 5% to 95%. The duty cycle range depends on the PWM frequency. The lower the PWM frequency the wider the duty cycle range that can be converted. 

Specifications:

  • PWM Range: 5Hz to 3KHz, selectable
  • PWM Amplitude: 5VDC to 24VDC typical, other are available.
  • Isolation: Input to Output to Power 1500VAC (test)
  • Accuracy/Linearity: +/-0.3% max., +/- 0.1% typ.
  • Operating Temperature: -40 Deg. C. to +50 Deg. C.
  • Temperature Effects: +/- 0.5% max., 0.2% typ. (for 40 Deg. C. change)