Function:
The IUC-7X-ACV converts a peak-to-peak AC voltage to a DC signal which can
be one of several industry standards (4-20 mA. 1-5VDC, etc). Isolation is between
input and output and power so that all three main circuits are isolated from
each other.
The Input has an upper cut-off frequency (3 dB point) which is typically at
1 KHz but may be specified for other frequencies. The input impedance of the
IUC-7X-ACV is 1 Megohm.
Typical applications are for vibration measurement using a displacement probe
that generates an AC peak-to-peak value within the 1KHz spectrum.
Specifications:
Isolation: Input to Output to Power 1500 VAC (test)
AC Measurement: Peak-to-Peak
Cut-off (3dB): 1KHz, unless otherwise specified
Accuracy/Linearity:+/- 0.3% max., +/- 0.1% typ.
Operating Temperature: -40 Deg.C. to +50 Deg.C.
Temperature Effects: +/-0.5% max., +/-0.2% typ. (for 40 Deg.C. change)